1. Introduction

Enterprise data centres underpin digital infrastructure, and the IT equipment inside them carries a large embodied carbon footprint. This paper puts figures on that footprint. Embodied carbon here means the emissions from life cycle stages A1–A5: raw material extraction, manufacturing, transport and installation. The figures are for enterprise data centres in Paris, France, at a power density of 10 kW per rack.

2. Scope and method

We express embodied carbon in two ways: per megawatt (MW) of IT load, meaning the total IT power capacity deployed, and per square metre (m²) of IT white space, meaning the floor area occupied by IT equipment. The figures draw on life cycle assessments (LCAs), Environmental Product Declarations (EPDs) and industry standards, including CIBSE TM65, the iMasons Climate Accord and Iron Mountain's sustainability research.

3. Embodied carbon estimates for IT equipment

3.1. Embodied carbon per MW of IT load

Component Embodied carbon (tCO₂e per MW) Main contributors
Servers 400–700 CPUs, DIMMs, motherboards
Networking equipment 100–250 Routers, switches, fibre-optic cabling
Storage devices 50–150 HDDs, SSDs, RAID enclosures
Racks and enclosures 30–80 Steel, aluminium
Cooling systems 150–300 CRAH/CRAC units, chillers, refrigerants
Total IT equipment 750–1,500 All of the above

Sources: CIBSE TM65, Iron Mountain, iMasons Climate Accord

3.2. Embodied carbon per square metre of IT white space

Power density (kW/rack) Embodied carbon (kgCO₂e/m²) Notes
5 kW/rack about 5,000–7,000 Lower density gives lower carbon per m²
10 kW/rack about 8,000–10,000 Higher density raises carbon per m² but reduces the overall footprint of the facility

Sources: CIBSE TM65, Iron Mountain

4. Where the embodied carbon in IT equipment comes from

This section says where each component's carbon comes from and what reduces it.

4.1. Servers

A server carries around 922 kg CO₂e of embodied carbon per unit. Chip fabrication is the main source: CPUs, DIMMs and motherboards take a great deal of energy to make, and frequent refresh cycles multiply that figure over the life of the facility. The two reduction measures are to extend server lifespan to 6–7 years and to upgrade modules instead of replacing whole units.

4.2. Networking equipment

Networking equipment accounts for 100–250 tCO₂e per MW. The carbon is in the fibre-optic components and in the large routers and switches. Consolidating network devices removes redundant hardware, and specifying equipment made by low-carbon manufacturing processes cuts the rest.

4.3. Storage devices

Storage devices account for 50–150 tCO₂e per MW. Hard disk drives (HDDs) are more carbon-intensive than solid state drives (SSDs), and RAID configurations add to material demand. Specifying SSDs improves efficiency, and compression and deduplication cut the amount of storage the facility needs in the first place.

4.4. Racks and enclosures

Racks and enclosures account for 30–80 tCO₂e per MW, and the carbon is in the steel and aluminium. Recycled material reduces it where it is available, and a space-efficient layout avoids installing more enclosures than the IT load needs.

4.5. Cooling systems

Cooling systems account for 150–300 tCO₂e per MW. The carbon is in the CRAH and CRAC units, the chillers and the refrigerants. Air-side economisation and liquid cooling reduce it, and a modular cooling design sized to the load avoids installing more plant than the facility needs.

5. Ways to reduce embodied carbon in IT infrastructure

Measure What it does
Life cycle assessments (LCAs) Identify the high-carbon components early.
Sustainable procurement Selects suppliers with low-carbon supply chains.
High server utilisation Reduces idle hardware and raises efficiency.
Extended hardware lifespan Lowering refresh rates from 3–5 years to 6–7 years reduces annual emissions.
Efficient cooling design Uses modular cooling, economisers and liquid cooling.
Low-carbon materials Gives priority to recycled aluminium and steel.
Circular economy practices Encourages refurbishing, resale and recycling.

Sources: CIBSE TM65, iMasons Climate Accord, Iron Mountain

6. Findings

On these figures the IT equipment in an enterprise data centre carries 750–1,500 tCO₂e of embodied carbon per MW of IT load, and servers, cooling systems and networking equipment are the largest contributors. Per square metre of IT white space the figure is 8,000–10,000 kgCO₂e/m² at the higher power density.

Servers carry the most embodied carbon of any component, at around 922 kg CO₂e per unit. Cooling systems account for 20–30% of the total, so cooling efficiency has a direct effect on the whole figure. Refreshing hardware less often and running servers at higher utilisation make a large difference to lifetime emissions. Modular IT and cooling designs avoid overbuilding, and recycled materials in racks and enclosures take the facility's footprint lower still. Procurement, design and operating decisions taken together can make a large reduction in a data centre's Scope 3 carbon footprint.

7. References

  1. CIBSE TM65, Embodied Carbon in Building Services
  2. iMasons Climate Accord, IT Equipment Carbon Transparency Initiative
  3. Iron Mountain, Lifecycle Carbon Impact of IT Equipment
  4. Schneider Electric, Data Centre Sustainability: Reducing Scope 3 Emissions
  5. Meta, Estimating Embodied Carbon in Data Centre Hardware
  6. Uptime Institute, Embodied Carbon in Data Centres: Challenges and Best Practices
  7. World Business Council for Sustainable Development (WBCSD), Net Zero Data Centres: Embodied Carbon Considerations